According to Malaysia's Department of Occupational Safety and Health (DOSH) the ventilation is considered adequate when the number of air changes every hour is not less than 10 under normal conditions (defined as "processes which generate little or no heat, smoke or fume") and no less than twenty ("should there be processes which generate heat, smoke or fume").3
The airflow inside the habitat should be arranged in a one-way flow with the inlet (at floor level) and outlet (at top level) on the farthest and opposite side. The habitat ventilation flow rate must be 2,000 cubic feet per minute from a clean source per welder to dilute the polluted air inside the habitat.
The United States Department of Labor OSHA claims that every type of job that raises workers deep core temperature (listed as higher than 100.4 degrees F (38°C)) raises the risk of heat stress, and provides a list of guidelines which might be used to manage work in these environments.4
A minimum positive pressure of 0.1 inch of water or 0.00025 bar (equivalent to 25 Pascal or 0.00363 PSI) shall be maintained inside the Habitat enclosure to prevent ingestion of hydrocarbon in the event of leak occurred outside.5[unreliable source?]
Many countries are members of the International Electrotechnical Commission (IEC). Positive pressure enclosures, or "welding habitats" are working on the principle of overpressure. This protection principle is regulated by IEC Standard 60079-13.6
The ATEX certification is the national certification standard of the European Union, and mandatory to operate equipment in explosive atmosphere in Europe. ATEX certification is not based on the IECEx certification scheme, certification is bases on the ATEX directive 2014/34/EU – see main article. Under the ATEX 2014/34/EU Directive, all equipment requires a proper manufacturer's EU Declaration of Conformity. For Zone 1 welding habitats this EU Declaration of Conformity must be based on a Notified Body issued EU–Type Examination Certificate for transportable ventilated rooms EN 50381.
Flammable gases are not generally explosive under all conditions, . Additionally, oxygen must be present.7 The flammability limits of gases are expressed in proportions to the other gases present. For example, for methane, research by Akifumi Takahashi et. al. shows limits between 4.4% for the lower explosive limit and the upper explosive limit at 16.3%.8 A positive pressure enclosure works by ensuring that the methane present in the work area never approaches the lower explosive limit.
The operating pressure inside a typical isolation chamber is set only marginally above local pressure; typically only 0.05 kilopascals (about 0.007 pounds per square inch) above local atmospheric pressure. This is low enough to be undetectable to operators working inside the enclosure (a person sitting in a bathtub full of water is exposed to higher pressures), but due to the leakages, it needs to ensure that the volume of air inside the enclosure is constantly changing. Intake air is drawn into the enclosure by fan units.
Łabanowski, Jerzy (2011). "Development of under-water welding techniques". Welding International. 25 (12): 933–937. doi:10.1080/09507116.2010.540847. ISSN 0950-7116. S2CID 137610663. http://www.tandfonline.com/doi/abs/10.1080/09507116.2010.540847 ↩
Halvorsen, Hugo (1 August 2015). "Working Together for Safety Recommendation 036E/2015 - Use of habitats" (PDF). samarbeidforsikkerhet.no. Archived (PDF) from the original on 4 December 2022. Retrieved 6 August 2023. https://samarbeidforsikkerhet.no/wp-content/uploads/2021/04/Recommendation-036E-Habitat.pdf ↩
"FACTORIES AND MACHINERY (SAFETY, HEALTH AND WELFARE) REGULATIONS 1970 (REVISED – 1983)". 28 February 1983. p. 12. Archived from the original on 16 August 2022. Retrieved 6 August 2023. https://www.dosh.gov.my/index.php/legislation/regulations/regulations-under-factories-and-machinery-act-1967-act-139/534-15-factories-and-machinery-safety-health-and-welfare-regulations-1970/file ↩
"Heat Stress Guide". osha.gov. Retrieved 6 August 2023. https://www.osha.gov/emergency-preparedness/guides/heat-stress ↩
admin (23 June 2022). "Pressurised Habitat Technician". Elite Offshore Pvt Ltd. Retrieved 6 August 2023. https://eliteoffshore.com/pressurised-habitat-technician/ ↩
"International Standard IEC 60079-13" (PDF). iec.ch. May 2017. Retrieved 6 August 2023. https://webstore.iec.ch/preview/info_iec60079-13%7Bed2.0%7Den.pdf ↩
Jones, G. W.; Kennedy, R. E. (1935). "Prevention of Gas Explosions by Controlling Oxygen Concentration". Industrial & Engineering Chemistry. 27 (11): 1344–1346. doi:10.1021/ie50311a027. ISSN 0019-7866. https://pubs.acs.org/doi/abs/10.1021/ie50311a027 ↩
Takahashi, Akifumi; Urano, Youkichi; Tokuhashi, Kazuaki; Hidekazu Nagai; Kaise, Masahiro; Kondo, Shigeo (1 September 1998). "Fusing ignition of various metal wires for explosion limits measurement of methane/air mixture". Journal of Loss Prevention in the Process Industries. 11 (5): 353–360. doi:10.1016/S0950-4230(98)00010-2. ISSN 0950-4230. https://www.sciencedirect.com/science/article/pii/S0950423098000102 ↩